The type DW-U is of simple robust construction and incorporates an adjustable switch point and analogue indication of flow and optical indicator by the means of a lamp.
APPLICATIONS
Ideal for warnings on cooling or lubrication systems.
MEASURING PRINCIPLE
The DW-U type flow switch incorporates the very reliable way deflection system. The fluid flow causes a pandulum system with its circular plate to move on a pivot against a spring. The metal bellows arrangement seals the measuring device from the flow medium and allows the pendulum movement to be trasformed. The Movement of the pendulum activates the measuring system, a 3 pole relay microswitch and a control lamp. The switch sends a signal to the flow control system. The flow switch design such that a high particle level within the flow is acceptable . However should the reducer o switch become blocked the unit will indicate “no flow”.
TECHNICAL DATA
Up to DN 50 (2”) supplied with “T”. Threaded (optional flanged).
Accuracy: up to 20 l/min ±5%; from 21 to 200 l/min ±4%; over 201 l/min ±3%.
Pressure loss: 0,1-0,5 bar.
Max viscosity: 200 c-stokes (viscosity to be advised with order).
Switch hystresis: 10% up to 2 bar pressure.
Operating Temperature : max 100°C.
Ambient Temp.: max 70°C.
Rating relay: 250 Vca, 5A.
Mechanical rating: IP55.